Backflow Preventer Assembly Type BA according to DIN EN 1717.
According to this standard the water quality falls into 5 classes depending on the degree of contamination.
This assembly provides protection against non-potable water up to class of risk 4; the ones which may be protected through a device.
The highest class of risk 5 has to be secured only through a free outlet.
IMT Backflow Preventers work according to the reduced pressure zone principle, the three-chamber system, where the intermediate pressure zone, separated from the other two through a check valve, can be vented to the atmosphere. This occurs automatically when the pressure drop between upstream and intermediate pressure zone reaches the value of 0,14 bar.
DVGW certified.

Backflow Preventer Assembly 1/2" and 3/4” consisting of:
Backflow Preventer Type BA Fig. 309 DVGW and KIWA certified
Test Cocksand Shutoff Valves

Forged Brass Body
Chrome Plated Test Cocks

 

Description

303k 

303KGLDH1H2SW
30304K 1/2“ 241 25 71 107 26
30306K 3/4“ 247 25 71 107 32

  

en gb    de de