302 – Disconnettorre tipo BA a completamento di rubinetti di erogazione da giardino o per idranti a colonna

pct   

This Backflow Preventer was designed according to DIN EN 1717.
According to this standard the water quality falls into 5 classes depending on the degree of contamination.
This assembly provides protection against non-potable water up to class of risk 4; the ones which may be protected through a device.
The highest class of risk 5 has to be secured only through a free outlet.
IMT Backflow Preventers work according to the reduced pressure zone principle, the three-chamber system, where the intermediate pressure zone, separated from the other two through a check valve, can be vented to the atmosphere. This occurs automatically when the pressure drop between upstream and intermediate pressure zone reaches the value of 0,14 bar.

  • Designed for application on extraction valves/bib cocks with hose connection.
  • Safety screw and protection cap against tampering.
  • The backflow preventer cartridge has an integrated filter to protect the device from dirt.
  • DVGW certified for application on standpipes.
  • Chrome Plated Brass Body
  • Structural Pressure PN 10 (145 psi)
  • Temperature Rating max. 65°C (149°F)
  • Short peaks max. 80°C (176°F)
  • Fluid: water
 

Description

302 

Dimensions in mm

302GG1HL
30204 3/4” 3/4” 102 82
30206 1”  3/4” 102 82
30208 1”  1” 102 82

  

en gb    de de