300 - Extraction Valve with integrated Backflow Preventer Type BA

eac   

Extraction Valve conceived for drain systems or outdoors applications (garden valve).
The assembly consists of a Ball Valve and a Reduced Pressure Zone Backflow Preventer Type BA according to DIN EN 1717.
According to this standard the water quality falls into 5 classes depending on the degree of contamination.
This assembly provides protection against non-potable water up to class of risk 4; the ones which may be protected through a device.
The highest class of risk 5 has to be secured only through a free outlet.
IMT Backflow Preventers work according to the reduced pressure zone principle, the three-chamber system, where the intermediate pressure zone, separated from the other two through a check valve, can be vented to the atmosphere. This occurs automatically when the pressure drop between upstream and intermediate pressure zone reaches the value of 0,14 bar.

Chrome Plated Brass Body
Chrome Plated Ball
With MULTILOGO black Handle with green round and long inserts
The backflow preventer cartridge has an integrated filter to protect the device from dirt.

Structural Pressure PN 10 (145 psi)
Temperature Rating max. 65°C (149°F)
Short peaks max. 80°C (176°F)
Fluid: water

 

Description

300 

Dimensions in mm

300GG1L1L2L3HH1H2
30004 1/2” 3/4” 75 58 100 145 40 105
30006 3/4”  3/4” 75 58 100 93 40 105
30008 3/4”  1”  75  58 100  93  40  105

  

en gb    de de